Seven input and output modules are provided for coupling SYSTEM-90E to digital process signals.
|
|
Some modules include special functions allowing the fast counting of pulses and
detecting of axis positions by way of touch probes and light strobes.
|
| |
| Digital inputs and outputs |
|
| |
DIO-6 |
DIO-6-A |
DIO-6-B |
DI-7 |
DO-8 |
MDI-3 |
MDO-4 |
| Inputs |
8 |
8 |
8 |
16 |
- |
32 |
- |
| Outputs |
8 |
8 |
8 |
- |
16 |
- |
32 |
| Special function |
|
2 channels fast pulse counters |
2 channels high-precision position detection |
|
|
|
|
| Connection |
Rugged pluggable screw terminals
 |
External connection modules (Phoenix Contact)
 |
|
| |
| Features |
|
|
 |
|
Fast pulse counters
DIO-6-A is a DIO-6 variant further including two 24-bit pulse counters for sensing fast
pulse trains with a frequency of up to 1 kHz. |
 |
|
High-precision position detection
DIO-6-B is a DIO-6 variant further including two channels for fast, high-precision
detection of axis positions by means of light strobes or touch probes.
Position detection is performed with a 20-µs accuracy which equals an 20-µm
accuracy at a speed of 1 m/sec. |
|
| |
| Inputs |
| designed as: |
optical couplers |
| Input 0 voltage: |
- 3.0 V to + 5.0 V |
| Input 1 voltage: |
+ 11.0 V to + 30.0 V |
| Input current: |
> 6 mA (turned on) |
|
|
| Outputs |
| designed as: |
MOS driver stages, 'plus' switching (galvanically isolated via optical couplers) |
| Amperage: |
0.5 A per output |
| Overload protection: |
Current limitation and shut-down when an excessive temperature condition occurs |
| Voltage supply: |
+ 24 VDC ± 25 % |
| Technical specifications subject to change without notice. |
|
|
| |
|
| |
|
|